Blog

Condition-Based Maintenance: Moving Beyond the Calendar Across a Multi-Site Estate

Most maintenance contracts in multi-site retail and hospitality still run on the calendar. An engineer visits each air handling unit, condensing unit and display case at a fixed frequency, whether that asset is running well or quietly failing. The visit is planned, budgeted and easy to audit. It is also blind to what happens in the weeks in between.

Condition-Based Maintenance: Moving Beyond the Calendar Across a Multi-Site Estate
6 October 2026

That gap matters more than it might seem. When researchers at the US Department of Energy’s Lawrence Berkeley National Laboratory (LBNL) analysed multi-year monitoring data from more than 60,000 pieces of HVAC equipment in commercial buildings, they found that on any given day 40% of air handling units (AHUs) and 30% of air terminal units had a reported fault of some kind. A quarterly or annual visit will catch some of those. Many will run for months before anyone notices.

Condition-based maintenance (CBM) changes the trigger. Instead of acting because a date has arrived, you act because the data says the asset needs attention. This article explains what CBM is, what the public evidence says it saves, which checks must stay on a fixed schedule in the UK, and what it takes to make it work across hundreds of sites.

Reactive, preventive and condition-based maintenance

Most estates use a blend of three approaches, and it helps to be precise about what triggers each one.

  • Reactive maintenance waits for a breakdown, a temperature excursion or a call from the store. Planning effort is low, but every failure arrives as an emergency, with call-out rates, disruption and, in food retail, the risk of lost stock.
  • Planned preventive maintenance (PPM) services assets at fixed intervals set by the manufacturer, the contract or an industry schedule. It is predictable, but it spends engineer time on healthy assets and cannot see faults that develop between visits.
  • Condition-based maintenance uses the measured or assessed condition of the asset to decide when work is needed. The European maintenance terminology standard, EN 13306, treats it as a form of preventive maintenance rather than an alternative to it. Predictive maintenance goes a step further by using trends to forecast when a condition will become a problem.

three maintenance models · trigger, timing and risk

CBM does not mean abandoning planned work. It means planned work is driven by evidence wherever the law and the asset allow, and reserved for fixed intervals where they do not.

What the evidence says about the savings

The most widely cited public figures come from the US Department of Energy’s Federal Energy Management Program (FEMP) Operations and Maintenance Best Practices Guide. It estimates that preventive maintenance saves as much as 12% to 18% on average compared with a reactive programme, and that a properly functioning predictive programme can save a further 8% to 12% over preventive maintenance alone. The same guide notes that, in the surveys it draws on, more than 55% of maintenance in the United States was still reactive.

US DOE FEMP O&M Best Practices Guide, 2010 · estimated savings by maintenance model

These are US estimates from a 2010 guide whose underlying studies are older and not named, so treat them as an indication of direction and scale, not a forecast for your estate.

Evidence specific to buildings points the same way. LBNL’s Smart Energy Analytics Campaign, which followed more than 100 organisations, found that those using fault detection and diagnostics (FDD), the analytics that sits behind most CBM in buildings, achieved median energy savings of 9% with a simple payback of around two years. Again, this is US data, but it is measured across real portfolios rather than modelled.

Why faults hide between visits

A fixed schedule works well when failures arrive on schedule. In building services they rarely do.

The LBNL study found that 21 different AHU faults were reported on at least 20% of the units in its dataset, and 18 persisted for more than 20% of the period covered. Most of these are not dramatic breakdowns. They are degraded operation: a damper stuck part open, a sensor drifting, a schedule that no longer matches trading hours, heating and cooling running against each other. Nothing trips, so nobody calls, and the asset carries on wasting energy and wearing itself out until the next planned visit or the first real failure.

That waste is measurable. The Carbon Trust’s guidance on heating, ventilation and air conditioning states that energy consumption can increase by up to 30% if regular maintenance is not undertaken. The same guide also points to one of the simplest forms of condition-based maintenance: fitting pressure gauges to show when filters need replacing, rather than changing them on a fixed date.

The same logic applies elsewhere. In refrigeration, rising discharge pressure, longer run times or slow recovery after defrost point to fouling, charge or airflow problems. In HVAC, supply air temperatures and runtimes show whether a unit is doing its job. That data often already sits in the building management system (BMS) or refrigeration controller; the challenge is reading it consistently and acting on it.

What must stay on the calendar

Condition-based maintenance is not a way of avoiding legally required maintenance. In Great Britain, several duties apply at fixed intervals whatever the asset’s condition.

  • F-gas leak checks. Stationary refrigeration, air conditioning and heat pump equipment must be checked at least every 12 months from 5 to 50 tonnes of CO2 equivalent (tCO2e), every 6 months from 50 to 500 tCO2e and every 3 months at 500 tCO2e and above. A leak detection system is mandatory at 500 tCO2e. Notably, the guidance states that installing a system to automatically detect leaks allows you to double the period between checks, a rare case where monitoring changes the statutory frequency.
  • Air conditioning inspections. In England and Wales, systems with an effective rated output of more than 12kW must be inspected by an energy assessor at least every five years, with a fixed penalty of £300 for not having a report.
  • Pressure systems. Under the Pressure Systems Safety Regulations 2000, a written scheme of examination must be in place before a system is operated. The Health and Safety Executive (HSE) gives a vapour compression refrigeration system with installed power over 25kW as an example of a system covered.
  • Duty holders must identify and assess sources of risk, manage and control those risks, and keep records, in line with HSE’s Approved Code of Practice L8.

GB statutory duties versus condition-led work · GOV.UK and HSE guidance

Rules differ in Scotland and Northern Ireland, and GB F-gas rules are under review, so check current guidance before changing any schedule. The practical approach is to keep a separate, fixed statutory register and apply condition-based triggers to everything else.

Building a condition-based programme across many sites

Running CBM on one building is an engineering exercise. Running it across 300 stores is an operating model. These are the steps that tend to decide whether it works.

  1. Start where data exists and failure is costly. Refrigeration packs and cases, AHUs and rooftop units usually already report data, and their failures carry the highest cost.
  2. Standardise the data first. A rule written for one unit type should run on every unit of that type. That only works if point names and asset types are mapped to a common model across sites and suppliers.
  3. Define triggers in engineering terms. A single threshold crossing is an alarm, not a condition. Good triggers combine duration, asset state, time of day and repeat occurrence.
  4. Validate before dispatch. Has the condition persisted? Did it clear itself? Is there already an open job for the same asset? Each of these checks removes a visit that would not have fixed anything.
  5. Put the diagnosis in the work order. An engineer who knows the likely cause and the affected asset arrives with the right parts and is more likely to fix it first time.
  6. Keep statutory work separate. Fixed-interval duties stay on a register that condition data cannot move, except where the regulation itself allows it.
  7. Measure and refine. Compare visits, repeat faults and first-time fix before and after, and feed engineer notes back into the rules.

Many service contracts are priced on visit frequency, so involve contractors early in how condition-led work is specified and paid for.

Where Conex OS fits

At multi-site scale, the hard part of condition-based maintenance is rarely the idea. It is the plumbing: getting consistent data out of several BMS vendors and generations of controllers, and turning it into the right job for the right contractor without adding another screen of alerts.

Conex Insight provides the foundation. It brings data from existing BMS platforms, refrigeration and HVAC controllers and IoT devices into one standardised estate model, so the same condition logic can be applied to every comparable asset. Its asset performance scoring helps teams see which assets show the strongest evidence that intervention is needed.

Conex Maintain turns condition into action. Its no-code rules engine lets engineering teams encode the checks that would otherwise sit in an experienced engineer’s head. Fault detection and alarm triage filter out self-clearing and duplicate alerts. Where the data confirms a genuine requirement, Conex Maintain raises a verified work order, with diagnostic context, directly in the customer’s computer-aided facilities management (CAFM) platform. The CAFM system still manages the work; Conex OS improves the decision about which work should exist.

condition signal to verified work order · 6 steps, 1 decision

Where maintenance automation removes unnecessary intervention, LoweConex programmes indicate a potential reduction in work order volumes of around 20% to 40%, and better diagnostic information has supported first-time fix improvements of up to around 40% in suitable applications. These are benchmarks rather than guarantees: results depend on the starting alarm volumes, telemetry quality and maintenance model. Conex OS does not replace statutory inspections or your BMS; it gives your team the evidence to time everything else.

Fewer, better-timed visits

The goal of condition-based maintenance is not fewer engineers or less care. It is engineering time spent where the data says it is needed, on the assets that are drifting, leaking or wasting energy, rather than on a rota that treats a healthy unit and a failing one the same.

The evidence suggests that moving from reactive to planned work, and then from planned to condition-led work, saves money at each step. It also shows where programmes fail: inconsistent data, triggers that are really just alarms, and work orders that tell the engineer nothing. Solve those, keep statutory duties fixed, and the maintenance budget starts to follow the condition of the estate rather than the calendar.

If you would like to see which of your scheduled visits your estate data could retime, talk to the LoweConex team.