Fault Detection and Diagnostics: Why More Alarms Is Not the Answer
Ask a maintenance manager at a large retail or hospitality estate whether they need more alarms, and the answer is usually a tired laugh. Their building management systems (BMS), refrigeration controllers and HVAC plant already generate more notifications than anyone can read.
The instinct is to treat that as a filtering problem. In practice it is a diagnosis problem. Faults in building systems are not rare events. When researchers at the US Department of Energy’s Lawrence Berkeley National Laboratory (LBNL) analysed fault data from 317 buildings, they found an average of 245 faults per building every month. The teams responsible for those buildings do not need to know about all of them. They need to know which ones matter, why they are happening and what to do next.
That is the job of fault detection and diagnostics (FDD). This article explains what FDD is, what the public evidence says it delivers, and why many multi-site estates struggle to get value from it.
Alarm, fault, diagnosis, action
The terms are often used interchangeably, but they describe different things, and the difference is where the value sits.
- An alarm tells you a value has crossed a configured threshold. A case temperature is above its limit, or a pressure is out of range.
- A fault is a confirmed problem with how equipment is behaving. It may or may not have raised an alarm, and one fault can raise many.
- A diagnosis explains the likely cause and the asset involved: a stuck damper, a failed sensor, a schedule that never switched off.
- An action is the decision about what happens next: who owns it, how urgent it is and what the engineer should bring.

alarm to action · 4 stages
A BMS is very good at the first step. FDD software analyses trend data from building systems using rules or models to do the next three. It looks for patterns that point to a genuine problem, such as simultaneous heating and cooling, a unit running outside its schedule, or a sensor reading that never changes, and ranks what it finds so people can act on the most important issues first.
What the public evidence says
The most useful independent evidence on FDD comes from LBNL’s Smart Energy Analytics Campaign, a multi-year programme backed by the US Department of Energy that tracked more than 100 organisations and over 6,500 buildings using building analytics.
Its 2020 report found that organisations using FDD achieved median energy savings of 9%, with results ranging from 1% to 28%. By comparison, organisations using meter-level energy information systems alone achieved a median of 3%. Median simple payback for FDD was around two years. A separate peer-reviewed study by the same research group found median savings of 8% across 550 buildings.

LBNL Smart Energy Analytics Campaign · FDD users, US
Two caveats matter. First, this evidence comes from US organisations, and the savings are measured at whole-building level rather than per fault. Public UK data on FDD outcomes is still limited. Second, the same research shows FDD is not a set-and-forget technology. In-house staff spent a median of eight hours a month per building working with the tool. The savings came from people acting on what the software found.
Why volume is the enemy
More data does not automatically mean better decisions. Past a certain point, it means worse ones.
Other industries learned this the hard way. In process industries, alarm management guidance published by EEMUA (the Engineering Equipment and Materials Users Association) and referenced by the Health and Safety Executive (HSE) sets a benchmark that, during normal operation, an operator should face no more than about one alarm every ten minutes. HSE’s own guidance cites an incident where operators had to recognise, acknowledge and act on 275 alarms in the final 11 minutes before an explosion.
Building services are not control rooms, and that benchmark does not transfer directly. But the principle does. When a helpdesk or remote monitoring team faces hundreds of alerts a day across an estate, three things happen:
- Alarm fatigue sets in. People stop reading alerts properly, and genuine faults are missed among the noise.
- Work orders multiply. Alerts that clear themselves, or that repeat the same underlying fault, still turn into tickets and visits.
- Engineers arrive under-informed. A job that says only “refrigeration alarm at store 123” gives the engineer little to prepare with, which makes a return visit more likely.
The LBNL data also suggests that a small number of fault types drive most of the volume. Preliminary analysis of air handling units across 1,526 buildings found that the ten most common faults accounted for 73% of all fault-months. That is encouraging: if you can prioritise and fix the recurring few, most of the noise goes with them.
What FDD actually finds
It is tempting to imagine FDD as a tool for spotting dramatic equipment failures. In practice, much of its value comes from finding ordinary, persistent waste that nobody had noticed.
The LBNL campaign asked organisations which measures they had implemented as a result of their analytics. The most common were operational rather than capital: correcting HVAC schedules, resetting supply air temperatures, fixing economiser operation, stopping heating and cooling from running at the same time, and adjusting space temperature setpoints.

LBNL 2020 · share of FDD-using organisations · 5 fixes
For a multi-site retailer or hospitality operator, this list will feel familiar. Plant running long after closing, a store where heating and cooling fight each other, a setpoint changed locally and never reset. Each is small in one building. Repeated across hundreds of sites, and left in place for months, they add up to real cost and to a steady stream of comfort complaints and call-outs.
Why FDD stalls across many sites
If the savings are real and the payback is quick, why is FDD not already standard across every large estate? The research is candid about the answer, and it has little to do with the analytics themselves.
LBNL found that interpreting the names of data points into a format FDD tools can read “typically involves labor-intensive efforts”. Participants described difficulty extracting data from older building automation systems, disparate naming conventions, and difficulty bringing all the data into a single database. Many also said they lacked the staff time to review findings and act on them.

four barriers to scaling FDD and the fix for each
Every one of those barriers gets harder with scale. A single office building has one BMS and one naming convention. A retail estate built up through acquisitions and refits might have several BMS vendors, multiple generations of refrigeration controllers, and a different point name for the same sensor in almost every store. UK evidence points the same way: Innovate UK’s Building Performance Evaluation programme found that installing a BMS without integrating it with other system controls caused “conflicts and confusion”, and that controls are often too complicated for people to use confidently.
The lesson is that FDD is only as good as the data foundation beneath it and the workflow after it.
What good FDD looks like in a multi-site estate
Whether you are starting out or reviewing an existing programme, these are the questions worth asking.
- Is the data standardised before it is analysed? A rule written for one air handling unit should work on every similar unit in the estate. That only happens if point names and asset types are mapped to a common model.
- Does it produce fewer outputs than inputs? The measure of success is a shorter, better-ranked list of issues, not a longer one. Look for duration checks, suppression of self-clearing alerts and grouping of related alarms.
- Does each fault come with a likely cause? An engineer should know what the fault probably is and which asset is affected before they set off.
- Is there an owner and a next step? Every confirmed fault should route to someone: the helpdesk, a contractor, an energy manager or a store.
- Does it connect to the tools people already use? FDD that lives in a separate portal adds another screen to check. FDD that raises a verified job in your CAFM system becomes part of the workflow.
- Is there a feedback loop? Closed work orders and engineer notes should improve the rules over time, so the same false positive does not come back next month.
- Does it respect statutory maintenance? FDD can reduce unnecessary calendar-based visits, but it should never be used to skip maintenance that is legally required.
Where Conex OS fits
Conex OS was built for exactly the conditions that make FDD hard: large estates, mixed equipment and more alarms than any team can read.
Conex Insight provides the foundation. It ingests data from existing BMS platforms, refrigeration and HVAC controllers and other devices across the estate, and standardises it into a consistent model, so an asset in one store can be compared with the same type of asset in every other.
Conex Maintain does the diagnostic work. Its no-code rules engine lets engineering teams encode the checks that would otherwise sit in an experienced engineer’s head: has the alarm persisted, did it clear itself, is the asset running, has a work order already been raised? Where the data confirms a genuine fault, Conex Maintain can raise a verified work order with diagnostic context directly into the customer’s CAFM platform. Your CAFM system still manages the work; Conex OS improves the decision about which work should exist.
Where maintenance automation removes unnecessary interventions, LoweConex programmes indicate a potential reduction in work order volumes of around 20% to 40%. That is a benchmark rather than a guarantee, and results depend on the starting alarm volumes, telemetry quality and maintenance model.
Fewer alarms, better decisions
The goal of fault detection and diagnostics is not to see everything. It is to know which few things matter today, why they are happening and who should deal with them.
The public evidence shows that FDD can pay back quickly when it is done well, and that most of its value comes from fixing ordinary, recurring problems. It also shows where programmes fail: fragmented data, inconsistent naming and teams without the time to act. Solve those, and FDD stops being another screen of alerts and becomes a steady flow of fewer, better work orders, with engineers sent to the right problem with the right information.
If you would like to understand how much of your current alarm volume genuinely needs an engineer, talk to the LoweConex team about reviewing a month of your estate’s alarm data. Get in touch with the team now on this page.
References
- Kramer, H., Lin, G., Curtin, C., Crowe, E. and Granderson, J. (Lawrence Berkeley National Laboratory). Proving the Business Case for Building Analytics. October 2020. Full report (PDF).
- Lin, G., Kramer, H. and Granderson, J. Building fault detection and diagnostics: Achieved savings, and methods to evaluate algorithm performance. Building and Environment, 168, 2020.
- Crowe, E. (Lawrence Berkeley National Laboratory). Fault prevalence in commercial buildings, US DOE Building Technologies Office peer review. 2023.
- Granderson, J. and Crowe, E. (Lawrence Berkeley National Laboratory). AFDD evaluation and fault prevalence, US DOE Building Technologies Office peer review. 2021.
- Health and Safety Executive. Better alarm handling (CHIS6). 2000.
- Health and Safety Executive. Alarm management. Updated 2024.
- Palmer, J., Terry, N. and Armitage, P. for Innovate UK. Building Performance Evaluation Programme: Findings from non-domestic projects. 2016.